Lesson 02 / 12 · Efficiency

Account for distribution losses

How much source power is needed to deliver 1,000 kW?

Run this browser lesson →

Predict before you run

Write down your prediction, then change only the input below. In the interactive lesson, compare the starting case with the challenge and export a worksheet to retain your reasoning.

The two lesson configurations
InputStarting valueChallenge value
Distribution efficiency0.95 ratio0.90 ratio

Reported quantity: kWh over 30 min. The live control accepts 0.5–1 ratio.

Worked answer

Divide the IT demand by efficiency. At 0.95 the source supplies 1,052.631… kW; at 0.90 it supplies 1,111.111… kW.

Reproduce the configuration

Starting case assumptions
IT demand / simulated duration1000 kW / 1800 s
Opening battery / energy capacity100 kWh / 100 kWh
Charging power limit100 kW
Charge / discharge efficiency0.95 / 0.9
Distribution efficiency0.95
Generator start delay30 s

Scheduled events

No failure or recovery events are scheduled.

The browser lesson applies its configuration to the normal preset. Open it above, run the starting case, switch to the challenge, and use “Verify against Python” to compare complete results. Use the worksheet export to keep the prediction, completed inputs and answer together.

Sources and verification

Original material by Mohammad Rezwan Khan, engine 1.0.0. Synthetic teaching cases; no facility calibration or independent external reproduction has been established. Annual PUE planning and outage continuity are different calculations. Full scope and evidence.